Permit Number: TC-COM-0526-00750
Parcel: 13316004D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0526-00750
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2026 Site Zoning APPROVED
06/02/2026 Site Engineering NOT REQUIRED
06/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/03/2026 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00750
ADDRESS/PARCEL: (6628 E TANQUE VERDE RD TUCSON, AZ 85715)-FORT LOWELL RD TUCSON, AZ 85705)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. Previously there was a request for archive drawings/permits and provided to the applicant.
a. The documents show that the last legal building permit for this space was done in 1993.
b. Since then, there was no permit applied for until this permit application for Primp Beauty + Salon.
c. Comparing the floor plans reveals that there are drastic differences. The space now encompasses square footage from exterior wall to exterior wall (previously half of this space used to be part of the adjacent space).
2. Please submit a complete set of drawings to include:
a. Site Plan showing the parking stalls and identifying the handicap stall/sign/accessible route and bicycle rack.
b. All drawings to be sealed/signed/dated by each discipline:
i. Architect (Please include the Reflected Ceiling Plan and Detail Drawings illustrating items such as the demising wall from slab to the underside of the roof deck, internal walls, reception desk at 34 inches high complying to ICC A117.1 sec 902.4, etc.)
ii. Mechanical Engineer
iii. Plumbing Engineer
iv. Electrical Engineer
v. Structural Engineer if applicable
c. MECHANICAL
i. The mechanical requirement for a beauty salon is more extensive.
ii. Code compliant exhaust system required for such use.
iii. Submit Mechanical Drawings to illustrate all of the above.
d. PLUMBING
i. The 3 wash sink require drawings illustrating the plumbing and waste lines.
ii. The 3 water dispense require drawings illustrating the plumbing and waste lines.
iii. Submit Plumbing Drawings that provides all plumbing information and their installation.
iv. Water Dispenser - Drinking Fountain shall be required per IBC Table 2902.1.
1. Where the Building and Plumbing Codes require a drinking fountain, the City of Tucson will accept point of use water dispenser in lieu of the classically recognized drinking fountain.
2. a. The water dispenser must be listed and labeled in accordance with the Code.
3. b. The water dispenser must be connected to a permanent supply of potable water.
4. c. The water supply must be indicated on the plans and installed per code.
5. d. A clear floor space shall be provided for the cooler in compliance with chapter 6 of ICC A117.1.
6. e. A permanently mounted disposable cup dispenser shall be installed adjacent to the cooler with the dispensing end between 34" and 48" above finish floor and show the clear floor space complying to chapter 3 ICC A117.1 section 602.4.
7. NOTE: waste line shall also be necessary to be connected to this drinking fountain
v. Service sink shall be required per IBC Table 2902.1. Please locate/label this on your Floor Plan.
e. ELECTRICAL
i. Submit the as-built information as requested by the Electrical Reviewer.
f. STRUCTURAL
i. Submit should it apply on this project.
3. Please resubmit.
06/01/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00750 (6628 E TANQUE VERDE RD TUCSON, AZ 85715)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide as-built electrical plans that show compliance with the NEC 210.8(B) for GFCI protection near sinks, drinking fountain and bathrooms.
06/08/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00750
ADDRESS/PARCEL: 6628 E TANQUE VERDE RD TUCSON, AZ 85715

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please provide as-built mechanical plans.
a. The plans shall identify all existing mechanical equipment, ceiling supply diffusers, return air grilles, exhaust fans (with the rated CFM), etc. (IBC 2024, Section 107.2.1)
b. Provide an outdoor air ventilation schedule. Show how the proposed mechanical system meets the minimum outdoor air ventilation and exhaust airflow requirements. (IMC 2024, Section 403.3.1.1)
06/08/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00750
ADDRESS/PARCEL: 6628 E TANQUE VERDE RD TUCSON, AZ 85715

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide as-built plumbing plans showing all existing water lines, drain lines, building sewer, water service, and related piping.
a. Please show that the wash bowls comply with section 412.10 of the 2024 IPC
06/06/2026 Fire New Construction REQUIRES RESUBMIT Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
06/08/2026 Water - PDSD REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00750
ADDRESS/PARCEL: 6628 E TANQUE VERDE RD TUCSON, AZ 85715

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please provide the size of the water meter, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2024.
05/26/2026 PDSD Application Completeness Express REVIEW COMPLETED