Permit Number: TC-COM-0526-00748
Parcel: 115180050

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0526-00748
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2026 Site Engineering Standard APPROVED Ref: TE-FPU-0626-00226
06/11/2026 Site Zoning Standard APPROVED
05/29/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/05/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-3042.
2. Indicate a 1-hour separation or provide fire sprinklers to comply with the 2024 IBC Table 509.1 requirements.
A. Please amend the plans to identify the approved, listed fire-resistance-rated assembly details for all fire-resistance-rated walls, floors, and ceilings. Provide the applicable listing numbers (e.g., UL, GA, or equivalent) and corresponding assembly details directly on the construction documents. Per 2024 IBC Sections 107.2.1 and 703.3.
B. Please amend the plans to show that all through-penetration and membrane penetrations of fire-resistance-rated assemblies are protected with approved firestopping systems. Provide detail drawings on the plans identifying the specific UL-listed (or equivalent) firestopping systems for pipe, conduit, and duct penetrations through rated walls, floors, and ceilings (e.g., putty pads, firestop sealants, collars, or sleeves, as applicable).Per 2024 IBC Section 714.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/04/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00748 (1601 N ORACLE RD Unit:BLDG 8 TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Reference sheet E1 and Sheet A2, Existing electrical panel. The provided space does not meet the required clear working space as required by NEC 110.26(A). Provide measurements showing working space is available or relocate this panel to a code compliant location. You cannot place appliances, shelving, storage or anything else within the required clear working space of the existing panel. The furred out wall around the panel would also violate the working space of the panel and probably violate the manufacturer’s installation listing and instructions.
2. Show and provide the required Dedicated Equipment Space as required by NEC 110.26(E)(1)(a). The plumbing cannot pass through this dedicated space.
3. Show on the plans what electrical work is new, existing, relocated, etc.
4. Provide electrical load calculations, for the Main Panel showing it can support the additional electrical load, Per NEC 220.40.
5. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
6. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
7. Provide an electrical plan and Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
06/12/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00748
ADDRESS/PARCEL: 1601 N ORACLE RD Unit:BLDG 8 TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide mechanical plans showing the existing mechanical system configuration. Reference: section 107.2.1, IBC 2024.
2. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
3. Please indicate whether space for clothes dryers is provided as well. Reference: Section 107.2.1, IBC 2024.
06/12/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00748
ADDRESS/PARCEL: 1601 N ORACLE RD Unit:BLDG 8 TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Central laundry rooms containing automatic clothes washers shall have floor drains to drain the entire floor area. The minimum drain outlet is 3”. Reference: Section 413.4, IPC 2024.
2. Clothes washers shall discharge through an interceptor. Reference: section 1003.6, IPC 2024.
06/12/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00748
ADDRESS/PARCEL: 1601 N ORACLE RD Unit:BLDG 8 TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide the size of the water meter serving this space and the total water demand that will be served by the water meter to verify that it can accommodate the new laundry room. Reference: Section 107.2.1, IBC 2024.
06/01/2026 Fire New Construction Standard REVIEW COMPLETED
05/22/2026 PDSD Application Completeness Express REVIEW COMPLETED