Permit Number: TC-COM-0526-00735
Parcel: 115180220

Address:
1475 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0526-00735
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2026 Commercial Building Standard APPROVED
06/09/2026 Commercial Plumbing Standard APPROVED
06/09/2026 Water - PDSD Standard APPROVED
06/09/2026 Commercial Mechanical Standard NOT REQUIRED
06/01/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/01/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00735 (1475 N ORACLE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The new, underground fire water pipe, is considered a Grounding Electrode per NEC 250.52(A)(1). This Grounding Electrode must be bonded to the existing building Grounding Electrode System, per NEC 250.50. See also 250.24(A)(1).
2. Show, also, that the existing metal fire sprinkler water pipes remain bonded to the System Grounding, NEC 250.104(A).
06/10/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
PDSD Zoning Review Section

PROJECT:
TC-COM-0526-00735 TD-DEV-0324-00070
1475 N. Oracle Rd. Tucson, AZ 85705
Annex Building Tucson House (1st Review)

TRANSMITTAL DATE: 6/10/2026

Comment: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

This site is located in the OCR-1 zone (UDC 4.7.26).

1. Comment: Site zoning has reviewed the plans for compliance with the associated Development Package (DP) TD-DEV-0324-00070. While it appears the building plans match the DP, Site Zoning cannot approve this permit until the revised DP is approved by all review agencies.
2. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
06/09/2026 Fire New Construction Standard REVIEW COMPLETED
05/20/2026 PDSD Application Completeness Express REVIEW COMPLETED
06/11/2026 Site Engineering Standard REVIEW COMPLETED