Permit Number: TC-COM-0526-00725
Parcel: 12112024C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0526-00725
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2026 Commercial Plumbing Standard APPROVED
10/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/05/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Comment not resolved. The balancing data for the air distribution of three of the four rooftop units is not shown. [Initial comment: Clarify the balancing information and the identification of the rooftop units. The Mechanical New Work Plan shows four 5-ton rooftop units with two supplying 2,000 CFM, one supplying 1,200 CFM, and one delivering 2,400 CFM. The Outdoor Air Calculation, however, shows a 10-ton unit (4,000 CFM), a 6-ton unit (2,400 CFM), and a 3-ton unit (1,200 CFM). Reference: Section 107.2.1, IBC 2024.]

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
09/24/2026 PDSD Application Completeness Express REVIEW COMPLETED