Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0526-00725
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2026 | Commercial Plumbing Standard | APPROVED | |||
| 10/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/05/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Comment not resolved. The balancing data for the air distribution of three of the four rooftop units is not shown. [Initial comment: Clarify the balancing information and the identification of the rooftop units. The Mechanical New Work Plan shows four 5-ton rooftop units with two supplying 2,000 CFM, one supplying 1,200 CFM, and one delivering 2,400 CFM. The Outdoor Air Calculation, however, shows a 10-ton unit (4,000 CFM), a 6-ton unit (2,400 CFM), and a 3-ton unit (1,200 CFM). Reference: Section 107.2.1, IBC 2024.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 09/24/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |