Permit Number: TC-COM-0526-00725
Parcel: 12112024C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0526-00725
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/20/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Clarify the balancing information and the identification of the rooftop units. The Mechanical New Work Plan shows four 5-ton rooftop units with two supplying 2,000 CFM, one supplying 1,200 CFM, and one delivering 2,400 CFM. The Outdoor Air Calculation, however, shows a 10-ton unit (4,000 CFM), a 6-ton unit (2,400 CFM), and a 3-ton unit (1,200 CFM). Reference: Section 107.2.1, IBC 2024.
2. The Outdoor Air Calculation includes a “Small Animal Cage Room (ventilated Cages).” Provide a detail showing how the individual cages are ventilated. The calculation calls for 150 CFM of exhaust for a 100 square foot area. Where is this area? What is the justification for not using Pet shops (animal areas), instead of the entries for veterinary offices? Reference: Section 403.3.1.1, IMC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
08/19/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Show how the existing water dispenser will be accessible to the public without having to pass through a storage room. Reference: Section403.3.1, IPC 2-24.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
08/07/2026 PDSD Application Completeness Express REVIEW COMPLETED