Permit Number: TC-COM-0526-00712
Parcel: 107090380

Address:
455 W MCIVER PL

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.6

Permit Number - TC-COM-0526-00712
Review Name: COMMERCIAL REVIEW - FULL v.6
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2026 Commercial Building Standard APPROVED
08/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/05/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide calculations to verify adequate ventilation of the office and the storage building: Reference: Section 403.3.1.1, IMC 2024.
2. Provide a list of the materials and the quantities of the materials that will be stored in the proposed storage building (i.e., is it an S-1 building or is it an S-2 building?).

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
08/05/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. A storage building requires a service sink. Show The location of the service sink and provide specifications for the service sink. Reference: Section 2902.1, IBC 2024 and Sections 303.4 and 402, IPC 2024.
2. Provide a metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 604.4, IPC 2024 and Section 606.4, ICC/ANSI A117.1-09.
3. Provide tempered water for the restroom lavatories with a device conforming to ASSE 1070. Reference: Section 419.5, IPC 2024.
4. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2024.
5. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5.1, IECC 2024.
6. TC-RES-0125-00299 shows the existing building sewer running south under the new storage building. Determine the material of construction of the existing building sewer and verify that it is allowed to be used under the proposed storage building. Reference: Section 702.3, IPC 2024. Show the location of the required cleanouts. Reference: Section 708, IPC 2024 and Pima County Standard Detail RWRD Detail RWRD 401, 2021.
7. Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2024, as amended by the City of Tucson.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
07/30/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-0426-00501(2nd Review)
Project: Commercial Solar
Location: 265 W VALENCIA RD
Review Date: 7/30/2026
Reviewer: Joe Macaulay – Civil Engineer - Site Engineering
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter review time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. Provide a response letter addressing each comment with location of change on the plans. Submit the separate response letter and plan set files.

Site Engineering Review Comments:
1. Floodplain use permit is in resubmit status due to cost estimate not satisfying requirements. Resubmit to the floodplain use permit with cost estimate. To this permit supply the following items:
2. Previous comment from Commercial Zoning V.1 and V.2 must be addressed:
Based on aerial photos, it appears that work has been done on the southeast quadrant of the parcel, including but not limited to pedestrian circulation, landscaping, shade structures, and playground equipment. City of Tucson staff were unable to find approved permit documents for these additions.
a. To address the prior additional site work, a Development Package will need to be submitted with this permit that includes a site plan. See the provided link for site plan examples https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Site-Plan-Examples

If you have any questions or concerns, please contact Joe Macaulay at Joe.Macaulay@tucsonaz.gov
08/13/2026 Site Zoning Standard REQUIRES RESUBMIT 1. COMMENT: Final Site Zoning approval for this building permit cannot be granted until the associated development package, TD-DEV-0726-00200, is first approved.

Contact Fernando Garcia, Lead Planner, Site Zoning at fernando.garcia2@tucsonaz.gov.
08/05/2026 Water - PDSD Standard REQUIRES RESUBMIT 1. Provide a reduced pressure backflow assembly to serve the office and storage building. Show the location on a site plan.
2. TC-RS-0125-00299 shows the existing 1” water service line connecting to the east side of the existing residence. TC-COM-0526-00712, however, shows the water service line connecting to the west side of the existing residence near the existing water heater enclosure. Verify the route, material, and size of the water service line. Reference: Section 107.2.1, IBC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
07/28/2026 PDSD Application Completeness Express REVIEW COMPLETED