Permit Number: TC-COM-0526-00711
Parcel: 120082470

Address:
4742 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0526-00711
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/14/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00711 (4742 S 6TH AV TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Power cannot be provided to a vacant lot unless there is a Development Package associated with the space, such as for a food truck court. This permit will not be approved until an approved Development Package is provided.
2. Show all wiring methods in detail for all new branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
3. Provide a panel schedule, showing the circuits that are being added. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
4. Update the electrical site plans and designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each new electrical outlet point. Designate the type of outlet it is, i.e. – receptacle, light, etc.., NEC arts;300 and 408.4. IBC 107.1.
05/14/2026 PDSD Application Completeness Express REVIEW COMPLETED