Permit Number: TC-COM-0526-00694
Parcel: 11918087A

Address:
3660 S 16TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0526-00694
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2026 Commercial Building Standard APPROVED
06/03/2026 Site Zoning Standard APPROVED
06/01/2026 Commercial Plumbing Standard NOT REQUIRED
05/20/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/03/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/22/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00694 (3660 S 16TH AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Show PV interconnection in compliance with NEC 705.32. Reference also NEC 230.95. 705.32 Ground-Fault Protection. Provide a GFCI PV backfeed breaker at the main panel/switchboard.
06/03/2026 Fire New Construction Standard REVIEW COMPLETED
05/12/2026 PDSD Application Completeness Express REVIEW COMPLETED