Permit Number: TC-COM-0526-00685
Parcel: 127122690

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0526-00685
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/25/2026 Outdoor Lighting REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0526-00685 (5765 E BROADWAY BL TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The provided lumen calculations are incorrect. Fixture ID L1 and L2 must be included in the total unshielded lumens and total(unshielded/shielded) lumen calculations.
a. The total unshielded lumens, as shown on the fixture schedules is 8,400 lumens, not 2,400. This is over the allowable unshielded total for this site. The yellow LED line, on the awning, is not compliant.
06/22/2026 PDSD Application Completeness Express REVIEW COMPLETED