Permit Number: TC-COM-0526-00669
Parcel: 12703012B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0526-00669
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2026 Commercial Mechanical Standard APPROVED
07/30/2026 Site Zoning Standard APPROVED
08/03/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/30/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0526-00669
ADDRESS/PARCEL: (5532 E SPEEDWAY BL TUCSON, AZ 85712)
TC-COM-0526-00787 (3002 E GRANT RD Unit:UNIT 2 TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. HOOD STRUCTURAL CALCULATION AND STRUCTURAL DRAWINGS
a. As discussed at the front counter, the above were to have been uploaded online. The City did not receive such documents, please upload the Structural calculation and Structural Drawings.
b. Ensure to submit the drawings containing keynote 10 on sheet S-4.
c. Ensure to submit the drawings containing the structural reinforcing detail 105 on sheet S-5.
d. Ensure to submit the drawings containing the hood attachments in detail 106 sheet S-5.
2. LIGHTING
a. Electrical Engineer’s response letter was not submitted. Please submit.
3. Please resubmit.
08/03/2026 Fire New Construction Standard REVIEW COMPLETED
07/09/2026 PDSD Application Completeness Express REVIEW COMPLETED