Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0526-00667
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2026 | Commercial Electrical Standard | APPROVED | |||
| 08/18/2026 | Outdoor Lighting Standard | APPROVED | |||
| 08/18/2026 | Site Engineering Standard | APPROVED | |||
| 09/08/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/02/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Provide justification for the cooling capacity of RTU-2. RTU-2 sees a cooling load of 42.8 MBH sensible but has a cooling capacity of 78.19 MBH sensible. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C403.3.1, IECC 2018.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 09/02/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Two hand sinks still discharge to the sanitary waste; connect them to grease waste or add the required signage. [Initial comment: A hand wash sink located in the kitchen area shall either discharge through a grease interceptor or have a sign posted above it stating: “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED”. Reference: Section 1003.3(A), IPC 2024 as amended by the City of Tucson.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 09/08/2026 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Krista Hansen Zoning Section Review PROJECT: TC-COM-0526-00667 - TD-DEV-0326-00053 1351 W. Prince Rd. Tucson, AZ 85705 New McDonald’s (2nd Review) TRANSMITTAL DATE: 9/8/2026 The site is located in C-2 zone (UDC 4.7.21). Food Service is an allowed use in this zone subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P (UDC Table 4.8-4). Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 1. Comment: Site Zoning has reviewed the building plans for compliance with the associated Development Package (DP) TD-DEV-0326-00053. While it appears the building plans match the DP, Site zoning cannot approve this permit until the DP is approved by all review agencies. 2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted. If you have any questions about this transmittal, please contact Krista Hansen at Krista.Hansen@tucsonaz.gov. |
||
| 09/02/2026 | Water - PDSD Standard | REQUIRES RESUBMIT | The domestic water piping plan, P1.0, and detail 7/P3.0 still show a backflow preventor for water service located within the building. Is this backflow preventor being installed in addition to the backflow preventor shown adjacent to the water meter on the development plan? [Initial comment: Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf ] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 08/13/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |