Permit Number: TC-COM-0526-00667
Parcel: 10607028B

Address:
1351 W PRINCE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0526-00667
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2026 Commercial Building Standard APPROVED
06/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/21/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00667 (1351 W PRINCE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide electrical load calculations, for the Main Panel showing it can support the additional electrical load, Per NEC 220.40. Sheet E4.2 shows a ‘Connected Amps’ greater than the rating of the MDP rating.
2. Clarify and show overcurrent protection between the ‘3 Phase Switchboard and the MDP, to protect the conductors, NEC 240.4.
Ensure overcurrent protection meets the requirements of NEC 408.36 for panel board, MDP.
3. Clarify load calculations for panels ‘Computer Panel’ and ‘LP-1. These both show a load calculation greater than the ‘Connected Amps’.
05/28/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C403.3.1, IECC 2018.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
05/28/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. A hand wash sink located in the kitchen area shall either discharge through a grease interceptor or have a sign posted above it stating: “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED”. Reference: Section 1003.3(A), IPC 2024 as amended by the City of Tucson.
2. If the discharge temperature of the dishwasher will be greater than 140 degrees Fahrenheit, show that the temperature rating of the drainage pipe material is suitable for the highest temperature of the wastewater or provide an approved tempering device for the wastewater. Reference: Section 702.5, IPC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
05/20/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0526-00667 (1351 W PRINCE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf


1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
2. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
3. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
6. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
7. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
8. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

9. Specify any exceptions used.

10. Provide Curfew lighting controls If applicable Per section 403.
05/22/2026 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0526-00667
Location: 1351 W PRINCE R
Review Date: 5/22/2025
Site Engineering Comments:
1. While Site Engineering has reviewed the plan set provided and compared to associated development page, Site Engineering will be unable to provide final approval to commercial permit TC-COM-0526-00667 until the associated development package TD-DEV-0326-00053 is fully approved and issued.

If you have any questions or concerns, please contact Marco Contreras at Marco.contreras@tucsonaz.gov
05/28/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0526-00667 - TD-DEV-0326-00053
1351 W. Prince Rd. Tucson, AZ 85705
New McDonald’s (1st Review)

TRANSMITTAL DATE: 5/28/2026

The site is located in C-2 zone (UDC 4.7.21). Food Service is an allowed use in this zone subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P (UDC Table 4.8-4).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Site Zoning has reviewed the building plans for compliance with the associated Development Package (DP) TD-DEV-0326-00053. While it appears the building plans match the DP, Site zoning cannot approve this permit until the DP is approved by all review agencies.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
05/28/2026 Water - PDSD Standard REQUIRES RESUBMIT 1. Show the location and size of the proposed water meter, backflow preventer, and the water service pipe on a site plan. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to the water utility. Reference: Section 107.2.1 and 107.2.6, IBC 2024.
2. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/01/2026 Fire New Construction Standard REVIEW COMPLETED
05/08/2026 PDSD Application Completeness Express REVIEW COMPLETED