Permit Number: TC-COM-0526-00666
Parcel: 117160030

Address:
119 E TOOLE AV

Review Status: Approved

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0526-00666
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2026 Commercial Electrical Express APPROVED Approved with comments added to the plans.



Where subject to physical damage, conductors, raceways, equipment, and cables shall be protected. NEC 300.4 Protection Against Physical Damage, NEC110.27(B) Prevent Physical Damage. Verify equipment is protected from physical damage or provide tire stops or bollards or other means to protect from car impacts.


The grounding and bonding shall include any existing Metal Water Line, Metal Support Structure, Concrete-encased Electrode, NEC 250.50.NEC 250.20(B), 250.24, 250.30(A)(1). Metallic gas lines must be bonded and not be used as the primary grounding method, NEC 250.50, 250.52(B)(1).
05/05/2026 PDSD Application Completeness Express REVIEW COMPLETED