Permit Number: TC-COM-0526-00666
Parcel: 117160030

Address:
119 E TOOLE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW REVISION v.1

Permit Number - TC-COM-0526-00666
Review Name: COMMERCIAL PDSD SIMPLE REVIEW REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2026 Commercial Post Review Express PENDING ASSIGNMENT
10/26/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0526-00666 (119 E TOOLE AV TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Electrical Review:

1. Provide an updated Engineer of Record’s seal with the date updated to match the revised drawings.
2. Show property line on the plans and show new electrical equipment and service entrance and disconnects are completely on the addressed parcel. Reference Sheet E2.0.
3. Show clear working space of the equipment does not cross property lines onto a separately owned parcel. A sealed Survey showing property lines and measurements may be required.
4. Where subject to physical damage, conductors, raceways, equipment, and cables shall be protected. NEC 300.4 Protection Against Physical Damage, NEC110.27(B) Prevent Physical Damage. Verify equipment is protected from physical damage or provide tire stops or bollards or other means to protect from car impacts. Reference Sheet E2.0, new service Termination Cabinet and disconnects in alleyway.
5. Reference Sheet E2.0, Keynotes #8. Note that the bottom of the conduits, over the roof of the buildings, shall be a minimum of 7/8” above the roof surface, NEC 310.15(B)(3)(c).
6. Show that the grounding and bonding shall include any existing Metal Water Line, Metal Support Structure, Concrete-encased Electrode, NEC 250.50. NEC 250.20(B), 250.24, 250.30(A)(1). Metallic gas lines must be bonded and not be used as the primary grounding method, NEC 250.50, 250.52(B)(1).
7. Show MIDWEST #UO1OG receptacle as GFCI protected in a Weatherproof cover.

Outdoor Lighting Review:
1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
2. The reflected ceiling plan on A2.0, and the lighting plan on E2.0 appear to show different lighting fixtures.
3. The string lighting on sheet E2.0, used on the outdoor patio are typically unshielded. Show, by providing the manufacture’s specification sheets, that these lights are full-cutoff and under a canopy, or meet all the requirements below, and provide lumen calculations for the entire site.
4. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different outdoor light sources on your lighting plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
5. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
6. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
7. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
8. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
9. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
10. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

11. Specify any exceptions used.

12. Provide Curfew lighting controls If applicable Per section 403.
10/26/2026 PDSD Application Completeness Express REVIEW COMPLETED