Permit Number: TC-COM-0526-00653
Parcel: 14118658A

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0526-00653
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2026 Commercial Electrical Standard APPROVED
07/21/2026 Commercial Mechanical Standard APPROVED
07/10/2026 Site Engineering Standard APPROVED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
07/21/2026 Commercial Plumbing Standard REQUIRES RESUBMIT A hand wash sink located in the café area shall either discharge through a grease interceptor or have a sign posted above it stating: “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED”. Reference: Section 1003.3(A), IPC 2024 as amended by the City of Tucson. [Previous comment: Show how the public sewer is to be protected from harmful discharges from the café (e.g., a grease interceptor). Reference: Section 1003.1, IPC 2024.]

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
07/17/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0526-00653 (10084 E OLD VAIL RD TUCSON, AZ 85747)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

>>> Outdoor lighting comments were not fully addressed. See additional comments below marked with ‘>>>’.

1. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
a. >>> Outdoor lighting fixtures G, GE, WW, WWE (Sheet E002, Lighting Fixture Schedule) shall be included in the outdoor lighting site plan/laminar schedule on sheet ES.2.
b.
2. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
a. >>> Not provided. Required.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
a. >>> Missing outdoor lighting calculation. Must provide calculations and all the information as required in the reference codes given. Missing. Required.
b. >>> Must declare the compliance option being used from Table 401.1.
c. >>> Must show/provide the developed area being used for calculations.
d. >>> total allowable lumens is (developed area) * (Lumens per acre based on compliance option chosen in Table 401.1).
e. >>> Must calculate the total allowable lumens and show that the total used lumens is less than this number.
4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
a. >>> The parking lot lighting fixtures are all shown with a color temperature greater than 3500K. Provide code compliant fixtures.
5. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
a. >>> Missing for G, GE, WW, WWE (Sheet E002, Lighting Fixture Schedule). Must also distinguish between fixtures ‘B’ & ‘D’ from Sheet ES.2, Luminar Schedule. All outdoor lighting fixtures should be included in this schedule.
b. >>> Clarify the ‘Luminaire Lumens’ for fixture ‘D’ on sheet ES.2. Is this lumen number per head or is it the total for the two heads?
6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.
a. >>> Missing. Required on the plans.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

7. Specify any exceptions used.
a. >>> Full cutoff fixtures under a canopy or overhang are exempt from Lumen Calculations total, but must be shown on the calculations as exempt.

8. Provide Curfew lighting controls If applicable Per section 403.
a. >>> Must be shown on the plans if applicable.
07/21/2026 Fire New Construction Standard REVIEW COMPLETED
07/01/2026 PDSD Application Completeness Express REVIEW COMPLETED