Permit Number: TC-COM-0525-01077
Parcel: 125110850

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0525-01077
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2025 Site Zoning Standard APPROVED
08/05/2025 Commercial Mechanical Standard NOT REQUIRED
08/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/06/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide a detailed description of the fire damage and the repair work involved in this permit’s scope. IBC 105.3 For example, is only the dry wall damaged, or what has been damaged?

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
07/22/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0525-01077 (3601 E 2ND ST Unit:UNIT 76 TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Panelboards shall not be located in the vicinity of easily ignitable material, such as in a clothes closet, NEC 240.24(D). Show Sub-panel ‘A’(2), in code compliant locations.
2. Show the door swing of the sub-panel. Clear working space must be maintained from the floor and for the dimensions in 2017 NEC 110.26(A). (no shelving or storage in this area).
3. Update the panel schedule to show the refrigerator circuit, #6, as also a Kitchen GFCI circuit as well, NEC 210.52.
4. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/05/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Coordinate the waterline isometric and the wastewater isometric with the layout of the plumbing fixtures as shown in the plumbing plans. Reference: Section 107.2.1, IBC 2018.
2. Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
07/21/2025 Fire New Construction Standard REVIEW COMPLETED
07/15/2025 PDSD Application Completeness Express REVIEW COMPLETED