Permit Review Detail
Review Status: Approved
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0525-01069
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2025 | Commercial Electrical Standard | APPROVED | Approved with comments added to plans: Provide two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, NEC [210.52(C)(1)] and NEC [210.52(B)(1)]. GFCI protected, NEC [210.8(A)] | ||
| 06/04/2025 | Bldg Permits - Post Review Express | REVIEW COMPLETED | |||
| 06/03/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |