Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0525-01061
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2025 | Commercial Building | APPROVED | |||
| 06/03/2025 | Commercial Electrical | APPROVED | |||
| 06/17/2025 | Site Zoning | APPROVED | |||
| 06/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/12/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Provide information on the sequence of operation for the restroom exhaust fan, EF-1, to show that all the air supplied to the restroom will be exhausted (i.e. the exhaust fan shall run whenever the supply fan is running during the hours of operation. Reference: Section 403.2.1 (4), IMC 2018. | ||
| 06/12/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The International Plumbing Code, 2018, is the controlling code for this activity, not the International Residential Code (see the water heater detail and Plumbing Specifications on P1). Reference: Section 101.2, IPC 2018. 2. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 3. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018. 4. Show the size, route, and termination of the T&P relief piping. Reference: Section 504, IPC 2018. 5. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (e.g., 24” for ½” supply piping). |
||
| 06/12/2025 | Water - PDSD | REQUIRES RESUBMIT | Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. | ||
| 06/04/2025 | Fire New Construction | REVIEW COMPLETED | |||
| 05/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |