| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2025 | Commercial Mechanical | APPROVED | |||
| 07/16/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/16/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Keynote 15 is not shown on the plumbing floor plan, and no hot water recirculation loop is shown at the new lavatory, P2. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (e.g., 24” for ½” supply piping).] | ||
| 07/15/2025 | Water - PDSD | REQUIRES RESUBMIT | Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter [Initial comment: Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.] | ||
| 07/01/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |