Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0525-01053
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/12/2025 | Commercial Building Standard | APPROVED | |||
| 06/03/2025 | Commercial Electrical Standard | APPROVED | |||
| 06/19/2025 | Site Zoning Standard | APPROVED | |||
| 06/17/2025 | Water - PDSD Standard | APPROVED | |||
| 06/03/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 06/19/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/17/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Provide specifications and balancing data for EF-1. Reference: Section 107.2.1, IBC 2018. 2. Provide calculations to verify that adequate ventilation will be provided for the dwelling unit. Reference: Section 403.3.2, IMC 2018. |
||
| 06/17/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Verify the terminations of the water heater T&P relief and the water heater pan drain. Reference: Sections 504.6 and 504.7.2, IPC 2018. | ||
| 06/04/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 05/27/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |