Permit Number: TC-COM-0525-01048
Parcel: 12405016A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-01048
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/12/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please show the address of each unit on the elevations and apply for another permit so each address has its own separate permit. IBC 107.2.1
2. Please amend plans to include a list of the year and name of the adopted applicable codes from the adopting ordinance. IBC 107.2.1 For example,
2018 International Building Code (IBC),
2018 International Existing Building Code (IEBC)
2024 International Fire Code (IFC)
2018 International Energy Conservation Code (IECC)
3. Please provide a plan view drawing of the upper patio showing that is a patio, or if it has been converted into a bedroom or other use, please provide complete design and drawings showing the new construction. IBC 107.2.1
4. Please provide construction drawings depicting the construction to take place with this permit. IBC 107.2.1 Please include the following, at a minimum
A. Framing details, material types and properties, fastening details. IBC Chapter 23
B. Provide details of the required weather-resistant exterior wall envelope. IBC 1402.2 Additionally, provide materials as directed by IBC 1403
C. Provide flashing details showing it will be installed in such a manner so as to prevent moisture from entering the wall or to redirect that moisture to the exterior. IBC 1404.4
D. Amend the plans to include insulation installation details. IECC C402.2.2 & Table C402.1.3

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
06/17/2025 Historic Standard REQUIRES RESUBMIT Staff has opened and completed initial review under the TC- COM-0525-01048 and opened the Historic sub-record. Please submit all the same materials under the Historic sub-record in a single compressed pdf file to apply for a SD #. Review fees will be invoiced for payment.
Attached is a link on how to get to the sub-record.
https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf
If you have any questions, contact Michael.Taku@tucsonaz.gov
06/17/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Krista Hansen
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-COM-0525-01048
701 E UNIVERSITY BL TUCSON, AZ 85719
Tenant Improvement (1st Review)

TRANSMITTAL DATE: 06/17/2025


This site is located in the HR-3 zone (UDC 4.7.10). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6.


01. COMMENT: Site zoning has no adverse comments on the proposed plans. This site is located within the West University HPZ. Zoning cannot approve this permit application until historic review and approval. Contact Michael Taku at Michael.Taku@tucsonaz.gov for further information.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments above, along with a detailed response letter indicating how all Site Zoning comments were addressed.


For questions regarding Zoning comments, please contact me at: Krista.Hansen@tucsonaz.gov
05/23/2025 PDSD Application Completeness Express REVIEW COMPLETED