Permit Number: TC-COM-0525-01026
Parcel: 113010090

Address:
1600 E ROGER RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0525-01026
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2025 Site Zoning APPROVED
11/10/2025 Commercial Building NOT REQUIRED No structural damage identified. See letter of assessment.
10/31/2025 Site Engineering NOT REQUIRED
11/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/28/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0525-01026 (1600 E ROGER RD TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

Electrical Review:
1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide an electrical plan showing any/all electrical work specific to the the scope of work being done at the buildings and site.
Plans shall include (as necessary for scope of work), but may not be limited to items below:
3. Provide electrical load calculations, for the Main Panels, Per NEC 220.40.
4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
5. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
6. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number.
7. Show all GFCI protection (NEC 210.8(B)) in readily accessible location per NEC 210.8.

Additional comments may be forthcoming with complete electrical plans for the building and site.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/24/2025 PDSD Application Completeness Express REVIEW COMPLETED