Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0525-01020
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2025 | Commercial Building Standard | APPROVED | |||
| 06/02/2025 | Commercial Electrical Standard | APPROVED | 414 E ARAGON RD only. | ||
| 06/02/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 06/10/2025 | Site Zoning Standard | NOT REQUIRED | |||
| 06/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/10/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Provide heating and cooling load calculations that justify the capacity of the heating and cooling equipment specified for the project. Reference: Sections R302.2, R403.7, and R503.1.2, IECC 2018 as amended by the City of Tucson. 2. Clarify the nature of the proposed air conditioning appliance: it is described as a heat pump but it is being supplied with natural gas. Show the complete specifications for the proposed air conditioning appliance, including the SEER2 (and HSPF2 if the appliance is a heat pump). Reference: Sections R103.2, R403.7 and R501.5, IECC 2018. 3. Provide a programmable thermostat that complies with the requirements of Section R403.1., IECC 2018. 4. Provide mechanical ventilation for the building. Reference: Section R403.6, IECC 2018. 5. Show how the air conditioning appliance is to be installed at grade (e.g., concrete slab). Reference: Section 304.10, IMC 2018. 6. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson. 7. Secure the refrigerant circuit access ports of the condensing unit to prevent unauthorized access. Reference: Section 1101.10, IMC 2018. |
||
| 05/20/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |