Permit Number: TC-COM-0525-01020
Parcel: 138160190

Address:
414 E ARAGON RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0525-01020
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/11/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. The Packaged Rooftop Air Conditioning Unit Schedule, SM-101, was not submitted. [Initial comment: Clarify the nature of the proposed air conditioning appliance: it is described as a heat pump but it is being supplied with natural gas. Show the complete specifications for the proposed air conditioning appliance, including the SEER2 (and HSPF2 if the appliance is a heat pump). Reference: Sections R103.2, R403.7 and R501.5, IECC 2018.
2. Packaged Rooftop Air Conditioning Unit Schedule, SM-101, not submitted. [Initial comment: Provide a programmable thermostat that complies with the requirements of Section R403.1., IECC 2018.
3. Packaged Rooftop Air Conditioning Unit Schedule, SM-101, not submitted. [Initial comment: Provide mechanical ventilation for the building. Reference: Section R403.6, IECC 2018..
4. Detail sheet DM-109 not submitted [Initial comment: Show how the air conditioning appliance is to be installed at grade (e.g., concrete slab). Reference: Section 304.10, IMC 2018.
5. Detail sheet DM-109 not submitted [Initial comment: Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
6. Note not shown on revised sheet M1.1. [Initial comment: Secure the refrigerant circuit access ports of the condensing unit to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
08/08/2025 PDSD Application Completeness Express REVIEW COMPLETED