Permit Number: TC-COM-0525-01008
Parcel: 11105030F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0525-01008
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2026 Outdoor Lighting Standard APPROVED
02/27/2026 Site Engineering Standard APPROVED
03/18/2026 Site Zoning Standard APPROVED
03/19/2026 Water - PDSD Standard APPROVED
03/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/16/2026 Commercial Building Standard REQUIRES RESUBMIT March 4, 2026
1st Review

Seaver Franks Architects
Attn: Nurlan Herberger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: OUR LADY OF LA VANG
SANCTUARY ADDITION (REVISIONS)

City of Tucson Permit Number: TC-COM-0525-01008
Stantec Project Number: 185215066
Stantec File Number: TUC-26-011

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 II-B 8,830 278 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Wood I joists.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, field welding, masonry and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Please provide a City of Tucson special inspection certificate with Parts A and B completed for the added masonry special inspection. Make sure that the owner or their legal representative signs the form.


STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/16/2026 Commercial Electrical Standard REQUIRES RESUBMIT March 4, 2026
1st Review

Seaver Franks Architects
Attn: Nurlan Herberger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: OUR LADY OF LA VANG
SANCTUARY ADDITION (REVISIONS)

City of Tucson Permit Number: TC-COM-0525-01008
Stantec Project Number: 185215066
Stantec File Number: TUC-26-011

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 II-B 8,830 278 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Wood I joists.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, field welding, masonry and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Please provide a City of Tucson special inspection certificate with Parts A and B completed for the added masonry special inspection. Make sure that the owner or their legal representative signs the form.


STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/16/2026 Commercial Mechanical Standard REQUIRES RESUBMIT March 4, 2026
1st Review

Seaver Franks Architects
Attn: Nurlan Herberger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: OUR LADY OF LA VANG
SANCTUARY ADDITION (REVISIONS)

City of Tucson Permit Number: TC-COM-0525-01008
Stantec Project Number: 185215066
Stantec File Number: TUC-26-011

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 II-B 8,830 278 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Wood I joists.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, field welding, masonry and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Please provide a City of Tucson special inspection certificate with Parts A and B completed for the added masonry special inspection. Make sure that the owner or their legal representative signs the form.


STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/04/2026 Commercial Plumbing Standard REQUIRES RESUBMIT March 4, 2026
1st Review

Seaver Franks Architects
Attn: Nurlan Herberger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: OUR LADY OF LA VANG
SANCTUARY ADDITION (REVISIONS)

City of Tucson Permit Number: TC-COM-0525-01008
Stantec Project Number: 185215066
Stantec File Number: TUC-26-011

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-3 II-B 8,830 278 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Wood I joists.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, field welding, masonry and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Please provide a City of Tucson special inspection certificate with Parts A and B completed for the added masonry special inspection. Make sure that the owner or their legal representative signs the form.


STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/18/2026 Fire New Construction Standard REVIEW COMPLETED
02/26/2026 PDSD Application Completeness Express REVIEW COMPLETED