Permit Number: TC-COM-0525-01006
Parcel: 11301146Y

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-01006
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2025 Site Zoning Standard APPROVED
05/27/2025 Fire New Construction Standard NOT REQUIRED
06/11/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/06/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Provide complete architectural plans, in addition to the structural plans that were provided, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1 City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Please prepare code-compliant construction drawings for this fire-damage repair project. Please address each area of damage and repair described in the damage assessment and locate these areas on the new construction drawings. IBC 107.2.1 For example, provide architectural drawings in addition to the structural drawings provided.
A. Provide a drawing, locating the damaged area on a roof plan.
B. Provide drawings, note or otherwise indicate the roof covering system to be used to repair the damaged areas of the roof covering.
C. Provide drawings to show the damage and repair to the electrical system.
D. Provide drawings to show the damage and repair to the mechanical system.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
05/19/2025 PDSD Application Completeness Express REVIEW COMPLETED