Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0525-01000
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/29/2026 | Water Sterilization Report (Deferred Submittal) Express | APPROVED | |||
| 09/29/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/29/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0525-01000 ADDRESS/PARCEL: 3800 W STARR PASS BL Unit:BLDG 1 TUCSON, AZ 85745 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. The letter from KC Mechanical appears to reference a different permit related to the Starr Pass Guest Rooms. The project number shown on the letter is 24195, while the project number on the current plan set is 24196. Also, Sheets M1.0 and M1.1 of the current plan set indicate that the existing VAV terminal units and air devices are to be balanced. Please provide an air balance report for the current project. Reference: Section 608.1, IMC 2024, as amended by the City of Tucson. |
||
| 09/29/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |