Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0525-00996
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2025 Commercial Electrical APPROVED
06/02/2025 Commercial Mechanical APPROVED
06/02/2025 Commercial Plumbing APPROVED
06/02/2025 Site Zoning APPROVED
06/02/2025 Water - PDSD APPROVED
05/20/2025 Outdoor Lighting NOT REQUIRED
06/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/31/2025 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0525-00996
ADDRESS/PARCEL: (7395 S HOUGHTON RD Unit:BLDG 0 UNIT 127 TUCSON, AZ 85747)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. Sheet TS1
a. The General Notes mentions 2000 IBC CABO as the codes being used.
i. The City of Tucson adopted the ICC 2018 International Building Code.
ii. Please remove any entries related to 2000 IBC CABO.
iii. Enter the 2018 IBC.
b. Code Study
i. We understand that you will be using the occupancy group G – Business.
1. The City will enter into the Certificate of Occupancy Document “Professional Services Business” per IBC 304.1 Business Group B.
a. Should you agree to this, please add it into your code study section.
c. Means of Egress
i. The city concurs with your analysis of requiring 2 exits since you have an occupant load of over 50.
ii. Exit at the Break room 106.
1. Extend the means of egress by extending the corridor through the Break room per IBC 1003.1 through 1003.6Restrooms Means of egress continuity.
a. Separate the corridor extension from the Break room by relocating the door and erecting a new wall.
d. Restrooms
i. Separate facilities shall be required in business occupancies over 25 occupant load (this facility has 55).
ii. Men’s
1. At 27.5, two water closets is required (shown is one).
a. Please correct this.
2. At27.5, one lavatory is required (shown is one).
a. This will be acceptable.
iii. Women’s
1. At 27.5, two water closets is required (existing is one).
a. Please correct this.
2. At27.5, one lavatory is required (existing is one).
a. This will be acceptable.
iv. Lavatories & water closets shall be handicapped accessible, ICC A117.1 & IBC 2902 compliant. Lavatory shall be maximum 34 inches above floor to the higher of the rim or counter surface, faucets and soap dispenser shall have a reach depth of 11 inches per ICC A117.1 section 606. Lavatory faucet operator shall also be metered & shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11 & 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Provide tempered water for the lavatory using an approved device conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018. Water supply and drain pipes under lavatories shall be insulated to protect against contact per ANSI 606.6 complying to clearances shown on Figure 606.3 ICC A117.1
2. Please resubmit.
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
05/21/2025 Fire New Construction REVIEW COMPLETED
05/16/2025 PDSD Application Completeness Express REVIEW COMPLETED