Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0525-00991
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/14/2025 | Commercial Electrical Express | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0525-00991 (6131 S MORRIS BL Unit:UNIT 1 TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf 2. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24. 3. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 05/14/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | ATTENTION: It appears the permit documents uploaded and permit location lists multiple units and each individual unit requires its own permit. This permit is for the identified main address 6131 S MORRIS BL UNIT 1 only, please start new permits for all other units. NOTE: Shared Studio Session 839-981-865 Master Permit TC-COM-0525-00991 Master meter being replace with individual meters. Same plans for each unit TC-COM-0525-00992, TC-COM-0525-00993, TC-COM-0525-00994 & TC-COM-0525-00995 |