Permit Number: TC-COM-0525-00990
Parcel: 12401010A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-00990
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2025 Commercial Electrical Standard APPROVED
06/05/2025 Site Zoning Standard APPROVED
06/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/02/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend the plans to include a life safety/means of egress plan. Please show complete egress plan of the second floor, with the path of travel and exit distance, exit signs and emergency lighting locations. IBC 107.2.3 For example, would occupants in the existing portion of the house use the exterior stairway? If so, the door swing from the existing structure to the proposed remodeled area is swinging in the wrong direction.
2. Please amend plans to show minimum 42” high guard at new extended landing. IBC 1015.3
3. Please amend the plans to show the required emergency illumination at the exterior stairway and landing. For example, a photometric plan or other method of showing 1 footcandle of normal power illumination at the walking surface along the path(s) of exit discharge, while the building is occupied. IBC 1008.2.1, IBC 1008.2.3 IBC 1008.1
4. Please amend the plans to provide a project-specific schedule of special inspections on the plan set. IBC 1704.1, IBC 1704.2.3, IBC 1704.3, & IBC 107.3.1
5. Please provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/03/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Clarify the description of the indoor mechanical units. The mechanical specifications call for heat pumps with wall-mounted ductless indoor units but the mechanical plan shows AC with ceiling-mounted cassettes. Reference: Section 107.2.1, IBC 2018.
2. Show the ventilation calculations for the bedrooms and “other spaces” (e.g. corridors and common areas. Reference: Section 403.3.2, IMC 2018.
3. Clarify how the ventilation air will be distributed in the space. Reference: Section 403.3.2.3, IMC 2018.
4. The COMcheck Mechanical Compliance Certificate is based on a single package heat pump, not the proposed HVAC equipment. Provide a COMcheck Mechanical Compliance Certificate that is based on the proposed HVAC equipment.
05/22/2025 Fire New Construction Standard REVIEW COMPLETED Fire Sprinklers upgrades requires a separate submittal and permit. Install smoke detectors as required by the 2024 IBC and IFC.
05/14/2025 PDSD Application Completeness Express REVIEW COMPLETED