Permit Number: TC-COM-0525-00984
Parcel: 10610129A

Address:
2023 W PRICE ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-00984
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2025 Site Zoning Standard APPROVED
06/05/2025 Water - PDSD Standard APPROVED
05/29/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the Outdoor Lighting.
06/13/2025 Site Engineering Standard NOT REQUIRED
06/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/04/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0525-00984
ADDRESS/PARCEL: (2023 W PRICE ST TUCSON, AZ 85705)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. BOOTH LOCATION - Please look at the Mechanical comments.
a. The distance from the property lines to the spray booth are not sufficient.
2. FLOOR PLAN
a. Please submit a floor plan illustrating the location of the paint booth within the building.
i. Please resolve the issue in item #1 above and reflect solution within the floor plan.
b. Locate and label the paint mixing booth.
c. Locate and label the paint storage.
i. Provide quantity of each product kept within the storage enclosure.
1. Include this information within your code analysis.
d. Locate and label the storage for leftover paint/flammable waste.
e. Show the spaces that are adjacent to this paint booth along with their occupant loads.
3. MEANS OF EGRESS
a. Provide a means of egress pattern on the plan drawing.
i. At the point of exit, indicate the distance traveled, the required exit width, the actual exit width and the number of people exiting.
b. Provide a door schedule enumerating the mechanisms/parts used such as panic hardware, door rating, latch mechanism, closer mechanism, etc.
4. CODE ANALYSIS
a. Provide a complete code analysis.
b. Provide the calculation for the occupant load.
5. SPRINKLER AND FIRE ALARM
a. Submit the fire sprinkler and alarm permit application to Tucson Fire Department for review and approval.
6. Please resubmit.
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
05/29/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0525-00984 (2023 W PRICE ST TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4. How is power getting from an existing panel to the new paint booth?
2. Provide new and updated panel schedules, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4.
3. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/05/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Revise the location of the paint booth exhaust termination as shown on the site plan to reflect the note on the roof detail that paraphrases Section 501.3.1, IMC 2018.
06/05/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the pipe sizes, existing and proposed loads and the developed lengths of the piping. Reference: Section 107.2.1, IBC 2018.
06/05/2025 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
05/15/2025 PDSD Application Completeness Express REVIEW COMPLETED