Permit Number: TC-COM-0525-00957
Parcel: 12109367A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0525-00957
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 7/1/2025 10:27:21 PM

Building(B) Reviewer (from previous submittal TUC9716001.051525)
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/22/2025 12:56:43 PM
07/02/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 6/28/2025 6:53:35 PM
07/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/02/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 7/1/2025 6:24:11 PM
1. (RESOLVED) - General - Provide existing RTU Schedule. - 2018 IECC Section C103.2Information on construction
documents. - 2018 IBC Section [A]107.2.1Information on construction documents.
2. (RESOLVED) - General - Provide COMcheck Mechanical Compliance Certificate. Any other APPROVED certifying
agency is acceptable. - 2018 IECC Section C403.3.2 HVAC equipment performance requirements.
3. (RESOLVED) - General - Specify on the drawings the outdoor air required by the 2018 IMC Section 403.3.1.1
Substantiate compliance by providing calculations on the drawings which indicates the floor area (sq. ft), maximum
occupant load, minimum required ventilation rate (cfm) for each occupancy, and total ventilation rate provided to the
occupied space.
4. (UNRESOLVED) - General - Provide Heat Load Calculations - 2018 IECC Section C403.1.1 Calculation of heating
and cooling loads
i. As per the Load calculations on plan sheet M601 the total coil load required is 213.9 MBH. The existing unit
schedule state with AHU 1, 2, and 3 the total coil load provided is 172 MBH. Existing systems do not meet the
required cooling needed for the space.
07/02/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 6/29/2025 2:28:48 PM
SECOND PLUMBING REVIEW: COMMENT 1 REMAINS
UN-RESOLVED-1). PLAN PAGE P100: MISSING PLUMBING FIXTURE MANUFACTURER NAMES & MODEL NUMBERS.
ADD MANUFACTURER NAMES & MODEL NUMBERS. TO THE FIXTURE SCHEDULE. -2018 IPC 303 ** INFO NOT
ADDED TO PLANS AND OR SPEC MANUAL NOT PROVIDED**
RESOLVED-2). PLAN PAGE P100 OR P101: MISSING SPECIFIC TYPE OF INDIVIDUAL BEVERAGE EQUPMENT
BACKFLOWS. ADD SPECIFIC TYPE OF INDIVIDUAL BEVERAGE EQUPMENT BACKFLOW DEVICES TO BE USED AT
EACH APPLIANCE . -2018 IPC 608.17.1
RESOLVED-3). PLAN PAGE I401: MISSING LAVATORY SIDE WALL CLEARANCE. ADD MISSING LAVATORY SIDE
WALL CLEARANCE. -2018 IPC 405.3.1
06/25/2025 PDSD Application Completeness Express REVIEW COMPLETED