Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0525-00948
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2025 | Site Zoning Standard | APPROVED | |||
| 06/05/2025 | Water - PDSD Standard | APPROVED | |||
| 05/22/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 06/09/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 06/11/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/11/2025 | Commercial Building Standard | REQUIRES RESUBMIT | May 29, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/ JaMia Dees 2552 N. Alvernon Way Tucson, Arizona 85712 Re: TUCSON FEDERAL CREDIT UNION 22ND STREET TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0525-000948 Stantec Project Number: 185215066 Stantec File Number: TUC-25-055 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B II-B 5,094 59 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS General 1. Sheet E1.0 of the electrical plans indicates that the existing fire alarm system will be maintained and relocated as required. Does this building also include fire sprinklers? Please indicate that the fire alarm system modification will be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal). If the building includes a fire sprinkler system be sure to include this as well as a separate permit. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 06/11/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | May 29, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/ JaMia Dees 2552 N. Alvernon Way Tucson, Arizona 85712 Re: TUCSON FEDERAL CREDIT UNION 22ND STREET TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0525-000948 Stantec Project Number: 185215066 Stantec File Number: TUC-25-055 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B II-B 5,094 59 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS General 1. Sheet E1.0 of the electrical plans indicates that the existing fire alarm system will be maintained and relocated as required. Does this building also include fire sprinklers? Please indicate that the fire alarm system modification will be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal). If the building includes a fire sprinkler system be sure to include this as well as a separate permit. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 06/11/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | May 29, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/ JaMia Dees 2552 N. Alvernon Way Tucson, Arizona 85712 Re: TUCSON FEDERAL CREDIT UNION 22ND STREET TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0525-000948 Stantec Project Number: 185215066 Stantec File Number: TUC-25-055 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B II-B 5,094 59 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS General 1. Sheet E1.0 of the electrical plans indicates that the existing fire alarm system will be maintained and relocated as required. Does this building also include fire sprinklers? Please indicate that the fire alarm system modification will be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal). If the building includes a fire sprinkler system be sure to include this as well as a separate permit. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 06/11/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | May 29, 2025 1st Review Seaver Franks Architects Attn: Rick Huch/ JaMia Dees 2552 N. Alvernon Way Tucson, Arizona 85712 Re: TUCSON FEDERAL CREDIT UNION 22ND STREET TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0525-000948 Stantec Project Number: 185215066 Stantec File Number: TUC-25-055 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms B II-B 5,094 59 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: None. ARCHITECTURAL COMMENTS General 1. Sheet E1.0 of the electrical plans indicates that the existing fire alarm system will be maintained and relocated as required. Does this building also include fire sprinklers? Please indicate that the fire alarm system modification will be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal). If the building includes a fire sprinkler system be sure to include this as well as a separate permit. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS There are no comments. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 05/21/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 05/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |