Permit Number: TC-COM-0525-00948
Parcel: 134113790

Address:
8145 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-00948
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2025 Site Zoning Standard APPROVED
06/05/2025 Water - PDSD Standard APPROVED
05/22/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/09/2025 Site Engineering Standard NOT REQUIRED
06/11/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/11/2025 Commercial Building Standard REQUIRES RESUBMIT May 29, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ JaMia Dees
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON FEDERAL CREDIT UNION 22ND STREET
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0525-000948
Stantec Project Number: 185215066
Stantec File Number: TUC-25-055

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-B 5,094 59 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Sheet E1.0 of the electrical plans indicates that the existing fire alarm system will be maintained and relocated as required. Does this building also include fire sprinklers? Please indicate that the fire alarm system modification will be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal). If the building includes a fire sprinkler system be sure to include this as well as a separate permit.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/11/2025 Commercial Electrical Standard REQUIRES RESUBMIT May 29, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ JaMia Dees
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON FEDERAL CREDIT UNION 22ND STREET
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0525-000948
Stantec Project Number: 185215066
Stantec File Number: TUC-25-055

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-B 5,094 59 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Sheet E1.0 of the electrical plans indicates that the existing fire alarm system will be maintained and relocated as required. Does this building also include fire sprinklers? Please indicate that the fire alarm system modification will be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal). If the building includes a fire sprinkler system be sure to include this as well as a separate permit.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/11/2025 Commercial Mechanical Standard REQUIRES RESUBMIT May 29, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ JaMia Dees
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON FEDERAL CREDIT UNION 22ND STREET
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0525-000948
Stantec Project Number: 185215066
Stantec File Number: TUC-25-055

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-B 5,094 59 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Sheet E1.0 of the electrical plans indicates that the existing fire alarm system will be maintained and relocated as required. Does this building also include fire sprinklers? Please indicate that the fire alarm system modification will be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal). If the building includes a fire sprinkler system be sure to include this as well as a separate permit.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/11/2025 Commercial Plumbing Standard REQUIRES RESUBMIT May 29, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ JaMia Dees
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON FEDERAL CREDIT UNION 22ND STREET
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0525-000948
Stantec Project Number: 185215066
Stantec File Number: TUC-25-055

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-B 5,094 59 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Sheet E1.0 of the electrical plans indicates that the existing fire alarm system will be maintained and relocated as required. Does this building also include fire sprinklers? Please indicate that the fire alarm system modification will be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal). If the building includes a fire sprinkler system be sure to include this as well as a separate permit.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.