Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0525-00944
Parcel: 141462210

Review Status: Requires Resubmit

Review Details: COMMERCIAL POOLS v.1

Permit Number - TC-COM-0525-00944
Review Name: COMMERCIAL POOLS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2025 Site Zoning APPROVED
05/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/30/2025 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0525-00944
ADDRESS/PARCEL: (7510 S PASEO GRAN ESCALERA TUCSON, AZ 85747)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. SECOND SHEET (no sheet number).
a. Provide sheet number.
b. Sheet contains 1. Spash Pad Plan, 2. Spash Pad Dimension Plan, 3. Spash Pad Section, second #3. Pad Drain Section, 4. Spash Pad Section.
i. There are two number 3 drawings.
1. Please correct this.
ii. Please correct the spelling for Splash Pad (you have it as Spash).
iii. The callout on drawing 1 Splash Pad Plan are both pointing to the same drawing 1/SP-1.
1. Please correct this.
iv. The sheet is void of information.
1. Please identify the parts of the installation.
a. If your drawing 4 Spah Pad Section is illustrating the Fill N’ Spill element please locate and label it.
i. Please do this in both the Splash Pad Section and the Splash Pad Plan. Identify all the parts.
ii. Do the same with drawing 3 Pad Drain Section. Identify the parts that are being installed similar to your drawing 2 on sheet SP-3 Fill N’ Spill Foundation Elevation.
iii. Where is the Touch & Go Activator. Locate and label this in your plans.
2. Rules and regulations be posted in a conspicuous location.
a. Provide information being provided and locate label in your plans.
3. Access to a water fountain.
a. Locate and label on your plan.
4. Access to restrooms.
a. Locate and label on your plan.
5. Emergency medical first aid kit shall be readily accessible.
a. Locate and label on your plan or provide location.
6. Warnings
a. Provide what is being provided.
b. Locate and label location on your plan.
7. Is there barrier/gate(s) being installed, if so please show it on your drawings.
8. All equipment grounded.
a. Ensure grounding is provided on every parts of this installation.
9. Per Arizona Administrative Code R18-5-218. Lighting
a. A public or semipublic facility and adjacent deck areas shall be lighted by natural or artificial means when they are in use.
b. A public or semipublic facility that is intended to be used at night shall be equipped with artificial lighting that is designed and spaced so that all parts may be seen without glare.
c. Please provide a special inspection certificate form with Part A, and Part B completed with next submittal. This form is available in https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-development-services/documents/special_inspection_certificate.pdf
i. Ensure that Part B is sealed/signed/dated by the special inspector in charge. Ensure to use Special Inspectors who are active in the approved list of special inspectors. They are available in the following links:
1. special-inspectors-by-name.pdf (orovalleyaz.gov)
2. https://content.civicplus.com/api/assets/e426f390-7bd6-4c47-9bc1-357282083afd
3. https://www.phoenix.gov/pddsite/Documents/TRT/dsd_trt_pdf_00870.pdf
10. Please resubmit
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
05/13/2025 PDSD Application Completeness Express REVIEW COMPLETED