Permit Number: TC-COM-0525-00930
Parcel: 10408053K

Address:
4525 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0525-00930
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 7/1/2025 10:16:19 PM


Building(B) Reviewer (from previous submittal TUC9712001.051425)
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/16/2025 10:37:52 AM
07/14/2025 Site Engineering Standard APPROVED
07/21/2025 Site Zoning Standard APPROVED
07/21/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/02/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 6/30/2025 4:22:17 PM
1. E4: Need to provide overcurrent protection for Panel E. None is shown in design.
Response: Transfer switch has a main breaker that is the OCPD.
Not Resolved.
E4: Show OCPD in transfer switch. If it isn't shown, it isn't there.
06/27/2025 PDSD Application Completeness Express REVIEW COMPLETED