Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0525-00930
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2025 | Commercial Building Standard | APPROVED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 7/1/2025 10:16:19 PM Building(B) Reviewer (from previous submittal TUC9712001.051425) Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 5/16/2025 10:37:52 AM |
||
| 07/14/2025 | Site Engineering Standard | APPROVED | |||
| 07/21/2025 | Site Zoning Standard | APPROVED | |||
| 07/21/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/02/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 6/30/2025 4:22:17 PM 1. E4: Need to provide overcurrent protection for Panel E. None is shown in design. Response: Transfer switch has a main breaker that is the OCPD. Not Resolved. E4: Show OCPD in transfer switch. If it isn't shown, it isn't there. |
||
| 06/27/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |