Permit Number: TC-COM-0525-00930
Parcel: 10408053K

Address:
4525 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-00930
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
John Graves
jgraves@mtcinspectors.com
Approved
Reason:
Date Completed : 5/19/2025 2:34:59 PM
05/28/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 5/26/2025 1:32:17 PM
First Plumbing Review: OK
06/02/2025 Water - PDSD Standard APPROVED
05/21/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/09/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/28/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 5/26/2025 12:51:08 AM
1. General / Updates: For project updates, submit sheets with all changes clearly marked in revision clouds. Please
provide a written response to each comment; updates without a clear response may not be reviewed. If you have any
questions regarding the comments, you may contact me directly. Updates may result in additional comments.
2. General / Special Inspection Certificate: Please have the Registered Design Professional in Responsible Charge of
this project complete and return the City of Tucson Special Inspections Certificate with signatures. The form can be
downloaded at: https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf
3. General / Current Code: The currently adopted building code for the City of Tucson is the 2018 International Building
Code. Please update the structural drawings to comply with this code.
4. Sheet S0.3 / Detail G6 / Sheathing & Boundary Fasteners: The Typical Plywood Panel Layout indicates where edge
boundary fasteners are required on sheathing for the proposed cold-formed steel stud walls. Fasteners are identified
in Detail G4, Note 8A. However, reviewer was unable to confirm the sheathing material and thickness or the required
spacing of edge boundary fasteners. Please confirm where this information has been provided.
5. Sheet S1 / A1 - Alteration Plan / Location of Mechanical Units: The location of Rooftop Unit #6 shown in the
Architectural and Structural Plan does not match the location shown in the HVAC Plan on Sheet M-1.1. Please
coordinate the location of mechanical units with all disciplines and revise drawings to be consistent.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/16/2025 10:37:52 AM
05/28/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 5/20/2025 5:32:35 PM
1. E4: Need to provide overcurrent protection for Panel E. None is shown in design.
06/09/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0525-00930
4525 N ORACLE RD

Site engineering comments are as follows:
1. Due to the proposed external changes, a development package will be required. UDC Article 3.3.3.G.2
2. Include trash truck maneuverability which complies with TSM section 8.

Tucson codes and ordinances can be found online at: https://codelibrary.amlegal.com/codes/tucson/latest/overview

Ryan Insalaco – ryan.insalaco@tucsonaz.gov
06/04/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0525-00930
4525 N ORACLE RD. - C-3
General Merchandise Sales (1st Review)

TRANSMITTAL DATE: ‎June 4, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

The site is in the C-3 zone (UDC 4.7.22). General Merchandise Sales is an allowed use in the zone (UDC Table 4-8-4)

1. Sheet C-1 Keynote 9 calls out “INSTALL NEW RAILING” at a proposed ADA Ramp, Keynote 6. Provide a detail that clearly demonstrates that all requirements of ICC A117.1, Section 405 & 505 are met.

2. Sheet C-1 Keynote2 calls out “NEW DUMPSTER LOCATION”. The addition of a new dumpster requires a new site plan, UDC Article 3.3.3.G.2.c, reconfiguration of an area outside a building.. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/21/2025 Fire New Construction Standard REVIEW COMPLETED
05/12/2025 PDSD Application Completeness Express REVIEW COMPLETED