Permit Number: TC-COM-0525-00927
Parcel: 12201027B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0525-00927
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2025 Outdoor Lighting APPROVED
06/02/2025 Site Engineering APPROVED
06/02/2025 Site Zoning APPROVED
06/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/02/2025 Commercial Building REQUIRES RESUBMIT May 14, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Ana Valenzuela
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON BOTANICAL GARDENS
NEW ENTRY

City of Tucson Permit Number: TC-COM-0525-00927
Stantec Project Number: 185215066
Stantec File Number: TUC-25-052

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,007 33 Yes No
M V-B 845
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, field welding, masonry.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system modification [2018 IBC Sec. 903] is to be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal).

2. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed for epoxy and expansion anchors, field welding, and masonry. Make sure that the owner or their legal representative signs the form.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/02/2025 Commercial Electrical REQUIRES RESUBMIT May 14, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Ana Valenzuela
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON BOTANICAL GARDENS
NEW ENTRY

City of Tucson Permit Number: TC-COM-0525-00927
Stantec Project Number: 185215066
Stantec File Number: TUC-25-052

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,007 33 Yes No
M V-B 845
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, field welding, masonry.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system modification [2018 IBC Sec. 903] is to be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal).

2. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed for epoxy and expansion anchors, field welding, and masonry. Make sure that the owner or their legal representative signs the form.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/02/2025 Commercial Mechanical REQUIRES RESUBMIT May 14, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Ana Valenzuela
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON BOTANICAL GARDENS
NEW ENTRY

City of Tucson Permit Number: TC-COM-0525-00927
Stantec Project Number: 185215066
Stantec File Number: TUC-25-052

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,007 33 Yes No
M V-B 845
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, field welding, masonry.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system modification [2018 IBC Sec. 903] is to be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal).

2. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed for epoxy and expansion anchors, field welding, and masonry. Make sure that the owner or their legal representative signs the form.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/02/2025 Commercial Plumbing REQUIRES RESUBMIT May 14, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Ana Valenzuela
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: TUCSON BOTANICAL GARDENS
NEW ENTRY

City of Tucson Permit Number: TC-COM-0525-00927
Stantec Project Number: 185215066
Stantec File Number: TUC-25-052

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,007 33 Yes No
M V-B 845
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, field welding, masonry.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system modification [2018 IBC Sec. 903] is to be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal).

2. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed for epoxy and expansion anchors, field welding, and masonry. Make sure that the owner or their legal representative signs the form.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/15/2025 Fire New Construction REVIEW COMPLETED The plans states that the building is equipped with fire sprinkler, add fire sprinklers coverage to the new proposed area. The addition of fire sprinklers requires a separate submittal and permit.
05/12/2025 PDSD Application Completeness Express REVIEW COMPLETED