Permit Number: TC-COM-0525-00926
Parcel: 11628001L

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-00926
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2025 Site Zoning Standard APPROVED
05/13/2025 Outdoor Lighting Standard NOT REQUIRED No outdoor lighting modifications.
05/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/16/2025 Commercial Building Standard REQUIRES RESUBMIT May 12, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS BALLROOM
REMODEL

City of Tucson Permit Number: TC-COM-0525-00926
Stantec Project Number: 185215066
Stantec File Number: TUC-25-051

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 67,000 278 Yes Yes
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Field welding.

ARCHITECTURAL COMMENTS

General

1. Please revise the sheet index to correctly label the Structural Section as it currently indicates Electrical for the structural sheet.

2. Please provide an occupant load for the remodeled areas. [Ref. IBC 2018 Sec.

3. Please provide a City of Tucson special inspection certificate with Parts A and B completed for field welding. Make sure that the owner or their legal representative signs the form.

Sheet A1.1

1. The design of the acoustic baffle ceiling is unclear. Detail 1 on Sheet S1.1 of the structural plan refers to architectural and interior designs for dimensions. These dimensions are not found on the architectural or interior design drawings. The design also appears to obstruct the existing fire sprinklers which would require modifications to the sprinkler system. Please indicate the modification of the existing fire sprinklers will be submitted as a separate permit on the cover page. [Ref. IBC 2018 Sec. 903.3.3]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/16/2025 Commercial Electrical Standard REQUIRES RESUBMIT May 12, 2025
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS BALLROOM
REMODEL

City of Tucson Permit Number: TC-COM-0525-00926
Stantec Project Number: 185215066
Stantec File Number: TUC-25-051

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 67,000 278 Yes Yes
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: Field welding.

ARCHITECTURAL COMMENTS

General

1. Please revise the sheet index to correctly label the Structural Section as it currently indicates Electrical for the structural sheet.

2. Please provide an occupant load for the remodeled areas. [Ref. IBC 2018 Sec.

3. Please provide a City of Tucson special inspection certificate with Parts A and B completed for field welding. Make sure that the owner or their legal representative signs the form.

Sheet A1.1

1. The design of the acoustic baffle ceiling is unclear. Detail 1 on Sheet S1.1 of the structural plan refers to architectural and interior designs for dimensions. These dimensions are not found on the architectural or interior design drawings. The design also appears to obstruct the existing fire sprinklers which would require modifications to the sprinkler system. Please indicate the modification of the existing fire sprinklers will be submitted as a separate permit on the cover page. [Ref. IBC 2018 Sec. 903.3.3]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/15/2025 Fire New Construction Standard REVIEW COMPLETED Any alterations to the fire sprinklers system will require a separate submittal and permit.
05/06/2025 PDSD Application Completeness Express REVIEW COMPLETED