Permit Number: TC-COM-0525-00923
Parcel: 11105016B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0525-00923
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2025 Commercial Mechanical Standard APPROVED
06/03/2025 Site Zoning Standard NOT REQUIRED
06/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/30/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0525-00923
ADDRESS/PARCEL: (3125 N ALVERNON WY Unit:BLDG 2 UNIT 211 TUCSON, AZ 85712)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. You are correct.
a. This facility falls in the category of commercial building permit type.
b. Yes, separate building permits will be required.
i. Please submit a building permit application for each dwelling unit.
ii. Each dwelling unit may differ in area.
1. Different dwelling unit area sizes will require various CFM and BTUH.
2. Please ensure to submit Manual J’s that the HVAC model and size will be correct for the dwelling size.
3. Provide drawings as to where the equipment is being installed such as the following.
a. Condenser and indoor unit if mini split is installed
b. Where condensate drain routed to
c. Provide GFCI & weatherproof receptacle at maximum 25 ft distance from unit on the same level.
d. Install a weatherproof disconnect. E3901.12
e. Provide information on separate/dedicated circuit
a. Provide panel schedule and load calculations
2. Please resubmit.
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
05/19/2025 Commercial Electrical Standard REQUIRES RESUBMIT Clarify in the scope of work if there is any modifications to any electrical systems.
05/09/2025 PDSD Application Completeness Express REVIEW COMPLETED