Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0525-00906
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/30/2025 | Commercial Building Standard | APPROVED | |||
| 05/16/2025 | Commercial Electrical Standard | APPROVED | |||
| 06/04/2025 | Site Engineering Standard | APPROVED | |||
| 06/02/2025 | Site Zoning Standard | APPROVED | |||
| 05/29/2025 | Water - PDSD Standard | APPROVED | |||
| 05/16/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the existing outdoor lighting. | ||
| 06/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/29/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. The ventilation calculations indicate that the restroom fan will be operating intermittently. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018. 2. The outside air and make-up airflow rates significantly exceed the exhaust airflow rates. Show how over-pressurization of the building will be avoided. Reference: Section 501.4, IMC 2018. |
||
| 05/29/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Sheets P100 and P101 have notes that are cut off by the viewport of the plan drawings. | ||
| 05/20/2025 | Fire New Construction Standard | REVIEW COMPLETED | Any upgrades to the fire sprinklers system or CO2 systems will required a separate submittal and permit | ||
| 05/08/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |