Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/08/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0525-00872 (2859 N FLANWILL BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide an electrical plan showing any/all electrical work associated with the fire repair.
Plans shall include, but may not be limited to items below:
3. Show all wiring methods in detail for all new or repaired branch circuit wiring and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/08/2025 Outdoor Lighting REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0525-00872 (2859 N FLANWILL BL TUCSON, AZ 85716)
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
2. Specify any Outdoor Lighting modifications that are being made, if any.