Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0524-01045
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/04/2025 | Welding Inspection (Deferred Submittal) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0524-01045 ADDRESS/PARCEL: (7391 E TANQUE VERDE RD TUCSON, AZ 85715) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. Structural Field Welding inspection incomplete. Inspection report says visual weld inspection was to be conducted, but there is no documentation. Only post installed anchors are listed. 2. Please resubmit |
||
| 02/04/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 02/04/2025 | Post-Installed Anchor Inspection (Deferred Submittal) Express | REVIEW COMPLETED |