Permit Number: TC-COM-0524-01045
Parcel: 114600480

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0524-01045
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2024 Site Zoning APPROVED
06/17/2024 Site Engineering NOT REQUIRED
06/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/18/2024 External Reviewers - Stantec REQUIRES RESUBMIT June 12, 2024
1st Review

Seaver Franks
Attn: Hillary Grigel/ Rick Huch
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: EDWARD JONES
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0524-01045
Stantec Project Number: 185215066
Stantec File Number: TUC-24-058

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,231 15 No Yes
Separate Permits: Fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors and field welding.

ARCHITECTURAL COMMENTS

General

1. Please remove the fire alarm system from the deferred submittal section. Fire alarm systems [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. Special inspection is required for epoxy and expansion anchors and field welding. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A0.0

1. The plumbing fixture calculations indicate that a water dispenser will be provided but no dispenser is shown on the floor plan or plumbing plans. Please clarify. {Based on the occupant load of 15, a drinking fountain is not required per. Section 2902.6 of the 2018 IBC.}

2. The plans do not include a service sink. Please revise plans to include a service sink. [Ref. IBC 2018 Sec. 2902.1

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

1. There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922