Permit Number: TC-COM-0524-01039
Parcel: 127090190

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0524-01039
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2025 Commercial Building Standard APPROVED
08/12/2025 Commercial Electrical Standard APPROVED
08/26/2025 Commercial Plumbing Standard APPROVED
08/26/2025 Site Zoning Standard APPROVED
08/26/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/26/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Provide calculations to verify that the replacement of the three DOAS units with make-up air units and five existing rooftop units will maintain the space temperature at not less than 68 degrees Fahrenheit on a design heating day. Reference: Section309.1, IMC 2018.
08/26/2025 Commercial Energy Standard REVIEW COMPLETED
08/19/2025 Fire New Construction Standard REVIEW COMPLETED
08/05/2025 PDSD Application Completeness Express REVIEW COMPLETED