Permit Number - TC-COM-0524-01034
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/01/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Show the union, check valve and ball valve on the discharge of the pump per the manufacturer’s instructions. [Initial comment: Provide a union, check valve and ball valve on the discharge of the pump per the manufacturer’s instructions. (The pump has a 1-1/2” discharge pipe.) Reference: Section 303.2 and 712.2, IPC 2018.] 2. A “sweet air filter” cannot be used on a vent that does not terminate outdoors. Terminate the vent outdoors to the open air. Reference: Sections 904.3 and 918.8, IPC 2018. [Initial comment: Provide a vent for the sump pump. Reference: Sections 303.2 and 901.1, IPC 2018.] 3. Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks (i.e. the stack shall turn horizontal for 20” before it connects to the horizontal branch). Reference: Section 704.3, IPC 2018. [Initial comment: Clarify how the horizontal gravity drain and its subsequent vertical stack will be connecting to the existing sanitary drain system. Reference: Section 107.2.1, IBC 2018.] |
||