Permit Number: TC-COM-0524-01034
Parcel: 117067100

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0524-01034
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/01/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Show the union, check valve and ball valve on the discharge of the pump per the manufacturer’s instructions. [Initial comment: Provide a union, check valve and ball valve on the discharge of the pump per the manufacturer’s instructions. (The pump has a 1-1/2” discharge pipe.) Reference: Section 303.2 and 712.2, IPC 2018.]
2. A “sweet air filter” cannot be used on a vent that does not terminate outdoors. Terminate the vent outdoors to the open air. Reference: Sections 904.3 and 918.8, IPC 2018. [Initial comment: Provide a vent for the sump pump. Reference: Sections 303.2 and 901.1, IPC 2018.]
3. Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks (i.e. the stack shall turn horizontal for 20” before it connects to the horizontal branch). Reference: Section 704.3, IPC 2018. [Initial comment: Clarify how the horizontal gravity drain and its subsequent vertical stack will be connecting to the existing sanitary drain system. Reference: Section 107.2.1, IBC 2018.]
07/15/2024 PDSD Application Completeness Express REVIEW COMPLETED