Permit Number: TC-COM-0524-01020
Parcel: 122060470

Address:
4301 E PIMA ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0524-01020
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2024 Commercial Plumbing APPROVED
06/06/2024 Site Zoning APPROVED
06/18/2024 Water - PDSD APPROVED
06/12/2024 Site Engineering NOT REQUIRED
06/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/18/2024 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0524-01020
ADDRESS/PARCEL: (4301 E PIMA ST TUCSON, AZ 85712)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Ensure that the facility is accessible complying to the ICC/ANSI A117.1 for both Employees and Customers internally as well as accessible route from drop off to front door. Provide drawings that illustrate the ANSI accessible counter at the cashier in both height and width requirements per 2009 ANSI A117.1 Figure 904.3(B).
2. Lavatories w/ knee guard, water closets shall be handicapped accessible, ANSI A117 compliant. Lavatory faucet operator shall also be metered. The metering faucet shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Code requires that accessibility be provided to the altered space. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area and signs. If these items are in full compliance with the current code, provide a statement indicating this on the cover sheet of the drawings. Otherwise, accessibility upgrades shall be required in accordance with IEBC.305.7.

If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs. If this exemption is taken, accessibility upgrades equaling 20% of the cost of the project shall be made. For example, the Restroom is not code compliant.
4. Please resubmit.
06/13/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Ref; Plan Sheet E2.0.

1 Provide a complete fault current analysis and provide the AIC ratings for the electrical service and new panel ‘K’.

2 The voltage ratings of the electrical equipment do not correlate with each other. The electrical line diagram shows the AC System voltage at 120/240 volts. The panel schedule for panel ‘MDP’ shows 120/208 volts. The panel schedule for panel ‘K’ shows 120/240 volts. The load summary shows 120/208 volts. Please clarify.

3 Please include new panel ‘K’ in the load calculations.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
06/18/2024 Commercial Mechanical REQUIRES RESUBMIT Spaces in which factory-built recirculating hoods tested in accordance with UL 710B are installed are considered to be kitchens and shall be ventilated per Section 403.3.1.1, IMC 2018. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual cooking appliance. The equipment plans show four cooking appliances, a roller grill, a microwave oven, an Unox oven, and a Turbo Chef oven. Reference: Section 507.1, exception 2, IMC 2018.
06/05/2024 Fire New Construction REVIEW COMPLETED
05/31/2024 PDSD Application Completeness REVIEW COMPLETED