Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0524-01018
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/13/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/13/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Please indicate the voltage of the new service on the Electrical Line Diagram. 2 Provide complete load calculations for the new electrical service. 3 Indicate the unit utilized in the MAX DC Charger specifications. (Highlight). Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 05/29/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |