Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/30/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
07/30/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The previous electrical plan review comments are not completely addressed. “Provide complete electrical plans “. 1 Provide manufactures cut sheet for the make and model of the EV Charger and Load Controller. If the spec sheet shows more than one model, be sure to Highlight the specific unit to be utilized. 2 Why is the OCPD crossed out in the Load Controller? This voids the ‘Wiring Detail’. 3 Provide a complete panel schedule for the ‘Sub Panel’ and the main service panel including load calculations. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
07/17/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |