Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0524-01002
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2024 | Commercial Building | APPROVED | |||
06/12/2024 | Commercial Electrical | APPROVED | |||
06/04/2024 | Site Zoning | APPROVED | |||
06/13/2024 | Water - PDSD | APPROVED | |||
06/06/2024 | Site Engineering | NOT REQUIRED | |||
06/14/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/13/2024 | Commercial Mechanical | REQUIRES RESUBMIT | The exhaust from the IT room is discharged into the plenum space. The discharge of environmental air is required to be discharged to the outside where it will not be drawn in to the ventilating system or cause a nuisance. Reference: Section 501.3, IMC 2018. | ||
06/13/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Indirect waste receptors (e.g. P-3) shall not be installed in concealed spaces. Verify the location of the proposed indirect waste receptor is visible for inspection and has ready access for cleaning. Reference: Section 802.4, IPC 2018. | ||
05/30/2024 | Fire New Construction | REVIEW COMPLETED | |||
05/28/2024 | PDSD Application Completeness | REVIEW COMPLETED |