Permit Number: TC-COM-0524-01002
Parcel: 12810054A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0524-01002
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2024 Commercial Building APPROVED
06/12/2024 Commercial Electrical APPROVED
06/04/2024 Site Zoning APPROVED
06/13/2024 Water - PDSD APPROVED
06/06/2024 Site Engineering NOT REQUIRED
06/14/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/13/2024 Commercial Mechanical REQUIRES RESUBMIT The exhaust from the IT room is discharged into the plenum space. The discharge of environmental air is required to be discharged to the outside where it will not be drawn in to the ventilating system or cause a nuisance. Reference: Section 501.3, IMC 2018.
06/13/2024 Commercial Plumbing REQUIRES RESUBMIT Indirect waste receptors (e.g. P-3) shall not be installed in concealed spaces. Verify the location of the proposed indirect waste receptor is visible for inspection and has ready access for cleaning. Reference: Section 802.4, IPC 2018.
05/30/2024 Fire New Construction REVIEW COMPLETED
05/28/2024 PDSD Application Completeness REVIEW COMPLETED