Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0524-00993
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2025 | Commercial Building Standard | APPROVED | |||
| 12/12/2025 | Commercial Electrical Standard | APPROVED | |||
| 12/29/2025 | Site Zoning Standard | APPROVED | |||
| 12/12/2025 | Outdoor Lighting Standard | NOT REQUIRED | |||
| 12/04/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 12/29/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/22/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Clarify the disposition of the existing exhaust fan for the pizza oven. The fan is removed on sheet D100 but appears to be retained on A100. | ||
| 12/22/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | On sheet A104, a new floor drain is shown by the Northeast corner of the existing oven (you really should correct your North arrow – it’s off 180 degrees). Where is the installation of this new floor drain shown? | ||
| 12/26/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 12/04/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |